Desktop|中文
Home About Us Products + News Center Technical Articles Messages Contact Us

Product Details

全自动Dielectric Loss Tester-扬州达瑞

Lightning Arrester Discharge Tube Tester - Yangzhou Dary

Published: 2020-08-23 14:04:49

Views: 2922

Category: ZnO Arrester Tester

Product Description
Lightning Arrester Discharge Tube Tester



Dary Electric recommends


Two-electrode discharge tube / lightning protection component tester



This instrument adopts a charging function for offline use, overcoming the disadvantage of traditional products that require plug-in power and are inconvenient for on-site operation. The voltage output of 2000V has a wider application range. It features high-voltage short-circuit protection, automatic discharge function, and is reliable, safe, and durable. At the same time, it uses a luxurious large color screen display, data storage, data review, pass/fail judgment, automatic shutdown, USB data upload, and other functions. The whole machine is beautiful and high-grade, with a wide range, high resolution, convenient operation, easy portability, accuracy, reliability, stable performance, and strong anti-interference capability.



It has anti-vibration, dust-proof, and moisture-proof structures, adapting to harsh working environments. It is a common and essential instrument for meteorological lightning protection, electric power, post and telecommunications, communication, mechanical and electrical installation and maintenance, as well as industrial enterprises that use electricity as industrial power or energy. It is suitable for measuring the performance parameters of various lightning arresters and surge protectors.



It is composed of medium and large-scale integrated circuits. This meter has high output power, with a starting action voltage measurement range of 10-2000V, leakage current measurement range of 0.1~199.9uA, good repeatability and stability, and one-key measurement for convenience and speed.


Measurement Function

Output Voltage

Measurement Range

Accuracy

Resolution

Varistor

Starting Action Voltage

U1mA

10~2000V

±2%rdg±3dgt

1V

Leakage CurrentI0.75,1mA

0.1~199.9uA

±2%rdg±10dgt

0.1uA

Discharge Tube

Discharge Voltage

10~2000V

±2%rdg±3dgt

1V

Insulation Resistance

500V

0~1000M

±3%rdg±10dgt

1M



Function                 Varistor, discharge tube discharge voltage and leakage current measurement, insulation resistance test

Ambient Temperature & Humidity         23℃±5℃,75%rh or less

Power Supply                 DC 7.2V, 6 rechargeable batteries, continuous standby for more than 3 hours

Measurement Method             DC voltage drop method    

Range Shift                 Fully automatic range shift

Backlight                 Yes

Display Mode             Color screen

LCD Size              108mm×65mm

Instrument Dimensions             Length x Width x Height: 240mm×188mm×85mm

Test Leads               Test leads: one red 1 meter, one black 1 meter, one green 1 meter

Measurement Stabilization Time         ≤3 seconds

Overvoltage Protection             Yes

Data Storage             500 groups, "H" storage indicator, "storage array" displays "500" to indicate storage is full

Data Review             "MR" symbol indicates when reviewing data



Note: The above information and technical parameters are compiled and released by Yangzhou Dary Electric Co., Ltd.




WeChat QR Code
💬
💬 Message ✕

Hello! Have you found what you need? Contact us directly online!

Leave a Message for Consultation
Yangzhou Darui Electric Co., Ltd.
主营产品:Dielectric Loss Tester、Transformer Ratio测试仪、Loop Resistance Tester、高压None线核相仪、Insulation Resistance Tester、Partial Discharge Tester、Cable Fault Tester、DC Resistance Tester等。
☎ Phone: 18952707000(关经理)📞 Landline: 0514-88770377✉ Email: 195214804@qq.com
Verification Code
By submitting, you agree to ourTerms of ServiceandPrivacy Policy