| Multifunctional Relay Protection Tester |
1. AC Current
Output range: 6×(0~30A)/phase or 3×(0~60A)/phase; max output power: 520VA/phase
Accuracy: error ≤0.1% for 0.2A~30A; error ≤0.2% for 30A~60A
2. AC Voltage
Output range: 6×0~130V/phase; max output power: 70VA/phase
Accuracy: error ≤0.1% for 2V~130V;
3. DC Current
Output range: -15~15A or 6×(0~15A)/phase; max output power: 150VA/phase
Accuracy: error ≤0.2% for 0.5A~15A;
4. DC Voltage
Output range: 0~300V or 6×(0~130V)/phase; max output power: 130VA
Accuracy: error ≤0.2% for 2V~300V;
Product Introduction
It is a six-phase relay protection tester launched by our company, stable and reliable. It automatically judges overcurrent, overvoltage, overload, short circuit, excessive temperature, abnormal data, and misoperation alarms. Six-phase microcomputer relay protection tester:
Six current outputs, six voltage outputs; Three-phase microcomputer relay protection tester: three current outputs, five voltage outputs; Both types have eight binary inputs and four binary outputs.
Product Features
① True color LCD integrated host, light weight, easy to carry;
② Built-in high-speed high-performance industrial computer, embedded operating system, stable and reliable operation; testing can be performed without external computer;
③ Panel embedded user-friendly buttons, also can connect external keyboard and mouse;
④ High-precision DAC can output 12 channels simultaneously, ensuring high waveform fitting accuracy and good linearity.
⑤ Optional electromagnetic compatibility components to enhance on-site anti-electromagnetic interference capability, can connect protection devices for electromagnetic compatibility tests;
⑥ Analog quantities are output on the front panel, switch quantity terminals are designed on the top cover, all wiring will not affect panel operation and test parameter monitoring;
⑦ Adopts designed heat dissipation structure to ensure good ventilation. Automatically judges overcurrent, overvoltage, overload, short circuit, excessive temperature, abnormal data, and misoperation alarms.
⑧ Uses company's technology voltage and current amplifiers to achieve AC/DC sharing, output stage adopts unique ultra-linear amplification technology, high accuracy, good reliability; simultaneously outputs six-phase AC voltage and six-phase AC current;
⑨ The device provides interfaces: RJ45 (Ethernet interface), USB interface (report transmission), industrial serial interface (for GPS or other serial devices).