How to Use a DC High-Voltage Generator?



1. Equipment Connection:

With the power disconnected, use the provided cables to connect the control box to the voltage doubler cylinder accordingly, then connect the ground wire, and finally plug in the power cord.

Note: All ground wires of the control box, voltage doubler cylinder, discharge rod, etc., must be connected to a single grounding point on the test object's ground wire. They must not be connected in series with each other.

2. No-Load Test to Check Equipment Integrity:

Before starting the test, perform a no-load test to check the integrity of the equipment.

After confirming the connections are correct, plug into the power outlet, turn the coarse and fine adjustment knobs fully to the left (the equipment has a zero-position protection function; voltage increase must start from zero, otherwise it cannot be increased), press the power switch, the green power indicator light will turn on, wait a few seconds for the system to stabilize, then press the start button. At this point, the red high-voltage indicator light will turn on, indicating that voltage can be increased.

After waiting a few more seconds, slowly turn the coarse adjustment knob clockwise. You will see the voltage meter reading rise. When the voltage reaches the desired value, release the knob. If the voltage value deviates slightly, adjust it by turning the knob.

Note: If the voltage meter reading does not change, immediately check whether the connections are correct. If it is an equipment malfunction, please call the service phone number on the cover to contact our company. Do not disassemble the equipment without authorization. After shutting down, for safety, use the discharge rod to discharge the high-voltage terminal of the voltage doubler cylinder before disconnecting wires.

3. Generally, after the test is completed, before shutting down, the voltage must first be adjusted to zero, then press the stop button. The red light will turn off, the green light will turn on, then turn off the power switch, unplug the power cord, and use the discharge rod to discharge.

If the above steps are normal, the equipment is intact and ready for testing.

Note: Wait at least one minute before turning on the equipment again.

4. Conduct Withstand Voltage or Leakage Test on the Test Object:

After verifying that the equipment is intact, connect the water resistor, microammeter, and the test object to the high-voltage terminal of the voltage doubler cylinder. After checking that the ground wires are correct, proceed with the test according to the above steps.

This equipment has overcurrent and overvoltage protection functions. If the high-voltage indicator light suddenly goes out during the test and the meter reading shows no high voltage, it means the protection circuit has been activated.