HDKY-CFSeriesBattery Banks



Product Overview;

HDKY-CF
SeriesBattery Bank Online Charge-Discharge Tester integrates online discharge, online charging, group activation, and monitoring functions into one unit.



Features;



Product Features:


●   Online constant current discharge function for batteries, with continuously adjustable discharge current.

●   Online intelligent charging function for batteries, meeting battery charging maintenance needs.

●   Online monitoring and rapid capacity analysis functions. Real-time online monitoring displays all test data: current, voltage, discharge time, capacity, etc.

●  Group activation function: can set the number of charge-discharge cycles for the entire battery bank, achieving online activation effect.

●  Cell monitoring function: cell voltage range: 1-20V, supporting 2V, 6V, 12V cell monitoring.

●  Full deep discharge function: supports ten-hour continuous discharge testing, accurately measures battery capacity, and automatically records test data.

●  Automatic shutdown function: automatically stops discharge/charge when any set threshold is reached, such as time limit, capacity limit, battery protection voltage, etc.

●  Protection function: automatically stops protection in case of abnormal voltage, etc.

●  On-site calibration function: allows on-site calibration of voltage and current.

●  Data storage function: automatically collects and saves charge/discharge data. After testing, data can be exported via USB drive to PC for analysis with dedicated software.

●  Backend PC analysis software with multiple analysis functions, capable of generating various test reports, providing basis for judging battery quality.

●   5.7-inch large touch screen: uses a large touch screen, allowing direct click operation on the screen, making operation simpler and clearer.

     During discharge, all discharge parameters can be viewed, and cell voltage bar charts can be displayed.



Technical Parameters;





Model HDKY-CF48150 HDKY-CF48300 HDKY-CF22060 HDKY-CF60060 HDKY-CF600100
Bank Voltage 18-60V 18-60V 170-270V 190-600V 190-600V
Discharge Current (Continuously Adjustable) 0-150A 0-300A 110V:0-30A
220V:0-60A
0-60A 0-100A
Charge Current (Continuously Adjustable) 0-150A 0-300A 110V:0-30A
220V:0-60A
0-60A 0-100A
Control Accuracy Discharge current ≤±0.5%; Bank voltage ≤±0.5%; Cell voltage: ≤±0.3%
Weight 11kg 18kg 18kg 23kg 38kg