| Induced Voltage Triple Frequency Generator |
Introduction
Yangzhou Dary provides triple frequency induced voltage generator manufacturer prices, triple frequency induced voltage generator manufacturer quotes, product selection, technical support, which is simple to operate, reliable in performance, and can better meet the needs of transformer and mutual inductor induced withstand voltage tests.
The induced withstand voltage test of transformers, mutual inductors, generators, motors and other equipment is an important test to ensure that the quality of the equipment meets national standards. The longitudinal insulation induced withstand voltage test of coil winding inter-turn, inter-layer, inter-segment and phase-to-phase insulation is an important item in electrical equipment insulation tests. Based on the particularity of the longitudinal insulation test, it is necessary to apply a frequency multiplier power device to increase the test voltage of the inter-turn insulation, thereby achieving the purpose of the withstand voltage test.
The SFQ-81 series triple frequency power generator is designed and manufactured to meet the above requirements. After extensive user use, it has been proven that it is simple to operate, reliable in performance, and can better meet the needs of transformer and mutual inductor induced withstand voltage tests.
Technical Parameters:
Input Voltage: 220V, 50Hz
Output Voltage: 50—500V (Max 750V), 150Hz
100—1000V (Max 1500V), 150Hz
Waveform: Sine wave, distortion less than 1%
Capacity: 1-1000KVA
Load Characteristics: Resistive, inductive, capacitive all applicable
|
Capacity KVA |
Input Voltage (Three-phase) |
Output Voltage |
Output Current |
Dimensions |
Weight |
|
5 |
220V |
400V |
20A |
450×250×320 |
40kg |
|
12 |
380V |
560V |
25A |
490×260×335 |
78kg |
|
24 |
380V |
640V |
30A |
680×280×400 |
150kg |
Triple Frequency Induced Voltage Generator Manufacturer Product Usage Method:
This device is a split type equipment. That is, the triple frequency power generator and the triple frequency control device, and is equipped with overvoltage protection, ammeter, triple frequency output, voltmeter for monitoring and ease of use. The wiring terminals on the back panel of the control device are shown in the figure below (connect this device into the circuit according to the wiring diagram, pay attention to equipment grounding)