Technical Specifications of On-resistance Tester
Test Current:  0.2A, 1A, 5A, 10A four ranges
Test Range:  0.2 A  10  Ω ~ 100Ω
            1A     100mΩ ~ 20Ω

            5A     10mΩ ~ 4Ω

            10A     1mΩ ~ 2Ω

Accuracy:    ±(Reading×0.2%+2 digits)
Maximum Resolution: 0.1μΩ
Operating Temperature: -5~40℃; Ambient Humidity: ≤90%RH, no condensation
Power Supply: AC220V±10%, 50HZ±1HZ
Dimensions: 390×280×200mm
Weight: 7Kg (excluding test leads)

Performance Features of On-resistance Tester
The instrument has large output current, wide measurement range, and is easy to operate;
The instrument has complete back-EMF protection function, audible discharge alarm, clear discharge indication, reducing misoperation;
The instrument is equipped with a printer, which can print test data at any time;
The instrument has a real-time clock, and can save and print test records together, convenient for users to save and review;
The instrument can permanently store 200 test data internally (expandable), and can also use USB flash drive to store data for easy import to computer for processing.
The instrument has the characteristics of wide applicable temperature, high precision, shock resistance, anti-interference, small size, light weight, and easy portability.

Safety Measures for On-resistance Tester
Be sure to read this manual carefully before using this instrument.
The operator of the instrument should have general knowledge of electrical equipment or instruments.
This instrument can be used indoors and outdoors, but should avoid places with rain, corrosive gases, excessive dust, high temperature, direct sunlight, etc.
The instrument should avoid severe vibration.
Maintenance, care, and adjustment of the instrument should be performed by professionals.
After testing, be sure to wait until the discharge alarm stops before turning off the power and removing the test leads.
During testing, it is forbidden to move the test clips and power supply lines.

On-resistance Tester
The reliable and effective connection between the grounding down conductor of power equipment and the grounding grid is the fundamental guarantee for the safe operation of equipment. The grounding down conductor is the connection part between the power equipment and the grounding grid. During the long-term operation of power equipment, the connection point may be affected by moisture and other factors, resulting in node corrosion, or even fracture, which increases the resistance at the connection point between the grounding down conductor and the main grounding grid, thus failing to meet the requirements of power regulations, causing potential safety hazards in equipment operation, and in severe cases, causing equipment to operate without grounding. Our company has developed a series of grounding down conductor on-resistance testers using our technical advantages. This instrument adopts new power supply technology, with the characteristics of small size, light weight, large output current, and automatic adjustment according to load size. The whole machine is controlled by a microcontroller, automatically completing self-check, data processing, display, printing, and other functions, with automatic discharge and discharge indication functions. The instrument has high test accuracy, is easy to operate, and can achieve rapid measurement of grounding resistance.



Precautions for On-resistance Tester

During testing, it is strictly forbidden to remove the test leads and cut off the system power.

Before removing the leads, be sure to wait until the discharge is completed and the alarm stops, then proceed to remove the leads.

If the test leads are not connected properly, the instrument will automatically prompt "Power supply open circuit". At this time, check whether the circuit is correct or not firmly connected, then press the reset button to re-measure.



Note: The above information and technical parameters are compiled and released by Yangzhou Darui Electric Co., Ltd.




WeChat QR Code
💬
💬 Message ✕

Hello! Have you found what you need? Contact us directly online!

Leave a Message for Consultation
Yangzhou Darui Electric Co., Ltd.
主营产品:Dielectric Loss Tester、Transformer Ratio测试仪、Loop Resistance Tester、高压None线核相仪、Insulation Resistance Tester、Partial Discharge Tester、Cable Fault Tester、DC Resistance Tester等。
☎ Phone: 18952707000(关经理)📞 Landline: 0514-88770377✉ Email: 195214804@qq.com
Verification Code
By submitting, you agree to ourTerms of ServiceandPrivacy Policy
🏠 网站Home📞 一键拨号✉ Contact Us