| Microcomputer Relay Protection Calibration Device |
AC Current Source
Six-phase current source with common neutral point, current rise and fall time <100μs
Maximum output power: 300VA/phase
Output accuracy:
0.1A to 2A accuracy ±10mA
2A to 10A accuracy ±0.2%
10A to 30A accuracy ±0.5%
Resolution:
0.1A to 10A resolution 1mA
10A to 30A resolution 5mA
Single-phase continuous output time:
0.1A to 5A output time unlimited
5A to 10A output time ≥60 seconds
10A to 20A output time ≥30 seconds
20A to 30A output time ≥3 seconds
AC Voltage Source
Six-phase voltage source with common neutral point, current rise and fall time <100μs
Maximum output power: ≥75 VA/phase
Output accuracy:
1V to 10V accuracy ±10mV
10V to 125V accuracy ±0.2%
Resolution:
1V to 10V resolution 1mV
10V to 125V resolution 5mV
DC Current Source
Single-phase output range: -10A to +10A or 0 to 20A
Maximum output power: 200VA/phase
Output accuracy:
±0.1A to ±2A accuracy ±10mA
±2A to ±10A accuracy ±0.5%
Resolution: 5mA
DC Voltage Source
DC voltage output range: -150V to +150V or 0 to 300V
Maximum output power: ≥100VA
Output accuracy:
±1V to ±10V accuracy ±20mV
±10V to ±150V accuracy ±0.5%
Resolution:
±1V to ±10V resolution 5mV
±10V to ±150V resolution 10mV
AC Voltage and Current Source Angle
Phase angle range: 0° to 360°
Accuracy: ±0.2°
Resolution: 0.01°
AC Voltage and Current Source Frequency
Frequency range: 10 to 1500Hz
Output accuracy:
10Hz to 65Hz ±0.005Hz
65Hz to 1500Hz ±0.02Hz
Resolution: 0.001 Hz
Can superimpose 2 to 20 harmonics of arbitrary amplitude and DC
Timing Accuracy
1ms to 1S ±10ms
1S to 999999S ±0.2%
Binary Inputs
Independent switch contact inputs, automatically recognize polarity of active contacts
15V to 250V active contacts
Binary Outputs
Programmable switch dry contact outputs: 250VDC, 0.5A or 250VAC, 0.5A
Synchronization
Voltage and current synchronization ≤50μS
Power Supply
AC input voltage
Rated value: 220V ±10%
Reference value: 220V ±2%
AC supply frequency:
Rated value: 50Hz ±10%
Technical Features
1. Uses easy-to-use Windows XP operating system, friendly human-machine interface, simple and quick operation. To facilitate user use, many keyboard shortcuts are defined, making operation "one-key to position".
2. High-performance embedded industrial control computer and large-screen high-resolution color TFT LCD display provide rich and intuitive information, including the current working status of the device, next-step work prompts, and various help information.
3. Equipped with ultra-thin industrial keyboard and touch mouse, all operations can be completed via keyboard or mouse just like operating a regular PC.
4. Equipped with external USB interface for convenient data storage and software maintenance.
5. Can complete all project tests without external devices, automatically display and record test data, and draw vector diagrams and characteristic curves.
6. Uses high-performance D/A converter, producing waveforms with high precision, good linearity, and good transient response and amplitude-frequency characteristics. Waveform accuracy and other indicators are guaranteed throughout the entire measurement range.
7. Can directly output AC voltage, AC current, DC voltage, DC current, with variable amplitude, phase angle, and frequency.
8. The power amplifier section uses a new type of high-power high-fidelity linear power amplifier circuit, with large output power and low ripple interference. Even when the output current reaches maximum, the waveform remains undistorted and without clipping.
9. The binary input interface can automatically adapt to passive (dry contact) and active inputs, and automatically adapt to the polarity of active inputs, working normally within the input voltage range of ±250V.
10. Can complete various complex calibration tasks, conveniently test and scan various protection settings, store test data in real-time, display vector diagrams, print reports, etc.
11. Adopts carefully designed chassis structure, small size, good heat dissipation, light weight, easy to carry, convenient for mobile testing.
Note: The above information and technical parameters are compiled and released by Yangzhou Dary Electric Co., Ltd.