YTC2135 On-site Voltage Transformer Tester
1 Scope of Supply
YTC2135 On-site Voltage Transformer Tester 1 unit
2 Standards Followed
Compliant with "Regulations for Handover and Preventive Tests of Power Equipment"
3 Basic Performance Parameters of the Product
3.1 Instrument Features
1. The YTC2135 Voltage Transformer Error Tester integrates both the low-voltage calibration method and the potential difference method for measuring voltage transformer errors, facilitating on-site verification of metering devices.
2. On-site verification of voltage transformers does not require standard voltage transformers, boosters, load boxes, or voltage-regulating control boxes. It uses extremely simple test wiring and operation to achieve verification of electromagnetic voltage transformers, greatly reducing work intensity and improving work efficiency, making on-site verification of transformers convenient.
3. The YTC2135 Voltage Transformer Error Tester has an internal standard voltage transformer with the same ratio as the tested voltage transformer, with an accuracy of 0.02 class, accurately measuring the ratio and no-load error of the tested voltage transformer. Then, combined with the test results of impedance and admittance, the error of the transformer is calculated.
4. Wide measurement range.
5. Has functions for testing voltage transformer ratio, DC internal resistance, and voltage load box.
6. Has testing function for dual-winding voltage transformers, equipped with two load boxes.
7. Uses a 640×480 high-resolution large-screen LCD display, with user-friendly interface and operation design, and touch screen auxiliary operation, making operation more convenient and faster.
8. Uses precise software algorithms to further improve the accuracy of measurement data.
9. Has intelligent judgment of external wiring conditions, prompting wiring errors, ratio errors, polarity errors, etc.
10. Automatically rounds test data and determines whether it exceeds tolerance. Out-of-tolerance data is displayed in reverse black, making the data characteristics of the transformer intuitive and clear.
11. Directly issues on-site verification conclusions, either qualified or unqualified.
12. Large-scale memory can store up to 1000 sets of on-site test data.
13. Equipped with a printer, can print test data on-site.
14. Uses engineering plastic mold casing, shockproof and pressure-resistant, ensuring the safety of operators and equipment during on-site high-voltage tests.
3.2 Technical Parameters
Parameters are detailed in: On-site Voltage Transformer Tester
4 Basic Configuration
1. YTC2135 Voltage Transformer Error Tester 1 unit
2. Test leads 1 pack
3. Power cord 1 piece
4. Technical documentation 1 set
Including: 1 user manual, user service card, product warranty card, and certificate of conformity, each one copy.
5 Acceptance
1) The instrument must undergo unpacking acceptance and on-site usage acceptance.
2) Unpacking acceptance items are as follows:
a. The instrument configuration complies with the technical contract requirements, no missing accessories, and the user manual and factory inspection report are complete.
b. The instrument has no damage, manufacturing defects, or moisture.
c. The instrument powers on normally and operates normally.
3) On-site acceptance is carried out according to the following requirements:
The instrument shall be used for actual measurement of the test object according to the on-site actual measurement requirements specified in the tender document, and if it meets the requirements, the test report shall be prepared in accordance with the technical agreement requirements.
6 Quality Assurance
Except for damage to the instrument and its accessories caused by human factors during on-site use, the quality guarantee period of the instrument is 3 years. During this period, defects caused by manufacturing reasons shall be eliminated free of charge by the manufacturer. After the quality guarantee period, if the instrument has defects, the manufacturer shall promptly cooperate with the user to eliminate the defects.